Compliance guide

Cool Room & Freezer Temperatures in Australia

What temperature a cool room, fridge or freezer should run at in Australia: the 5°C rule, common set points, alarm limits and the records to keep.

By Abid Khan, founder · 12 October 2026 · 7 min read

Short answer

Potentially hazardous food must be kept at 5°C or below, and frozen food must stay frozen hard. That is why a food cool room is usually set to run at 1–4°C and a freezer at −18°C or colder. The law sets the temperature of the food, not the number on the thermostat.

Kitchen managers, butchers, supermarket teams and pharmacists all ask the same question when they commission a new unit or fail an inspection: what number should it be set to? The honest answer has two parts. There is a legal limit on the food, and there is a set point on the equipment that keeps the food inside that limit. Mixing the two up is the most common reason a cool room passes on paper and fails in practice.

This guide gives the limit, the usual set point and a sensible alarm limit for each kind of unit, explains why the air and the product disagree, and covers what your record needs to show.

What the law actually says

Standard 3.2.2 of the Food Standards Code requires a food business to store potentially hazardous food under temperature control. FSANZ explains that this means 5°C or colder, or 60°C or hotter, unless the business can show that a particular food stays safe at another temperature.

For frozen food the rule is different. If food is meant to be stored frozen, the business must make sure it remains frozen. The FSANZ guide to the standards, Safe Food Australia, says the freezer must keep the food hard frozen and that no temperature for frozen storage is specified.

So the Code does not mention 3°C, 4°C or −18°C. Those numbers are how operators stay inside the legal limit, and they are industry practice. State authorities say the same thing in their own words: the NSW Food Authority repeats the 5°C and 60°C limits and the requirement that frozen food stays frozen during storage and display.

Vertical temperature scale showing safe food storage limits: freezer at or below -18°C, fridge at or below 5°C, hot holding at or above 60°C and poultry cooked to a core of 75°C

Set points by unit

The legal column comes from the sources above. The set point and alarm columns are common practice, not law. Your own food safety program, the equipment manufacturer and the product label take priority.

Unit Legal or guideline requirement Common set point Typical alarm limit
Cool room (food) Potentially hazardous food at 5°C or below 1–4°C Air above 5°C for 20–30 minutes
Walk-in freezer Food intended to be frozen remains frozen; no temperature specified −18°C to −22°C Air above −15°C for 30–60 minutes
Reach-in kitchen fridge Potentially hazardous food at 5°C or below 2–4°C Air above 5°C for 15–30 minutes
Display fridge or deli cabinet Potentially hazardous food displayed at 5°C or below 1–3°C Air above 5°C for 20–30 minutes
Drinks fridge (no potentially hazardous food) None for food safety 3–7°C, for quality Optional, for example 10°C
Vaccine fridge Strive for 5: +2°C to +8°C, aiming for +5°C +5°C Below +2°C or above +8°C
Pharmacy medicine fridge The storage conditions on each product’s label, usually 2–8°C 4–5°C Below 2°C or above 8°C

The alarm limit sits between the set point and the legal limit, never beyond it. A cool room set to 3°C with an alarm at 5°C leaves a two-degree band for normal swings, and the delay stops a routine defrost from waking someone at 2am. Because product warms more slowly than air, an air alarm at 5°C reaches you while the food itself is still under 5°C, which is the point of having one.

Open-front display cabinets are usually set colder than a closed fridge because the air curtain lets warm shop air in. Vaccine fridges are a separate case: the National Vaccine Storage Guidelines ‘Strive for 5’ say domestic refrigerators, including bar, commercial and industrial fridges, must not be used for vaccines, and call for a purpose-built vaccine refrigerator with an alarm below +2°C and above +8°C.

Why the air and the product read differently

A sensor on the wall measures air. The Code measures food. The two drift apart for predictable reasons.

  • Defrost cycles. Most cool rooms and freezers defrost several times a day. The air can rise a few degrees for 15 to 30 minutes while the product barely moves, because a full shelf of stock holds its temperature far better than air does.
  • Door openings. A busy service or a delivery with the door propped pushes warm air in. The air reading jumps first and recovers quickly once the door shuts.
  • Loading warm stock. A pallet that arrived at 5°C, or a tray that has not finished cooling, will sit above the room temperature for hours. A room set to 3°C can hold product at 6°C if it is overloaded and the air cannot circulate.

This is why Safe Food Australia recommends checking the food itself with a probe or infra-red thermometer rather than relying on the refrigerator’s gauge, and checking different areas of the unit, because one item within limits does not mean every item is.

When product does go above 5°C, the clock that matters is the 2-hour/4-hour rule. Add up every minute ready-to-eat potentially hazardous food has spent between 5°C and 60°C. Under two hours, it can go back into cold storage. Between two and four hours, use it or sell it straight away. Over four hours, throw it out. That rule runs on product temperature, so a short air spike during a defrost does not start it. A failed compressor overnight almost certainly does.

Where to measure

Put the sensor where the product sits, not in the coldest spot in the room. In practice that means:

  • mid-shelf height, on a wall or shelf post among the stock;
  • away from the evaporator fan, which blows the coldest air in the room and will make the unit look better than it is;
  • out of the direct draught from the door;
  • in a large room, a second sensor near the door, where readings move first.

If you need product temperature rather than air temperature, put a probe in a product simulant. The FSANZ guide’s own example is a bottle of water in each cool room and fridge, checked daily with a probe thermometer. Vaccine fridges follow the same idea: Strive for 5 places the thermometer probe in an empty vaccine box in the centre of the fridge.

The placement guidance on our cold room monitoring page goes into sensor counts for larger rooms. Whatever you use to measure potentially hazardous food, Standard 3.2.2 requires the thermometer to be accurate to plus or minus 1°C.

What the record must show

Standard 3.2.2A applies to food service, catering and related retail businesses that handle unpackaged, ready-to-eat potentially hazardous food. Category one businesses must make a record that substantiates storage under temperature control, and the FSANZ guide suggests a daily record of the temperature and the date. Records must be kept for 3 months. A data logger graph counts as a record, as does a sheet, as long as it is available when an authorised officer asks.

A useful storage record shows:

  1. the date and time of each check;
  2. which unit, named the same way every time;
  3. the reading, and whether it was air, a simulant or the food;
  4. whether it was within the limit written on the record;
  5. any corrective action, what happened to the stock, and who did it.

Our free fridge, freezer and coolroom temperature log is laid out that way. Even businesses outside category one usually need something similar in their food safety program.

Vaccine fridges have stricter rules. Strive for 5 asks for the current, minimum and maximum temperature to be recorded manually twice daily, even when a data logger is fitted, and for the logger to be downloaded and reviewed at least weekly. The Strive for 5 vaccine fridge temperature chart follows that format.

Making the numbers hold overnight

Twice-daily checks prove the unit was fine at opening and close. They say nothing about 3am on a Sunday, which is when most compressors fail. A wireless sensor in each unit records a reading every few minutes, alerts the person on call when a limit is crossed, and turns the history into the storage record.

Thermalog starts at $361 ex GST for a Cloud Gateway and $179 ex GST per sensor, with monitoring at $4 per sensor per month. See pricing for the kits and a cost calculator.

Set the limit from the food, set the thermostat to keep the food inside it, set the alarm between the two, and write down what you find. That covers almost every question an inspector will ask about your cool room.

Questions people ask

Is 7°C OK for a cool room?

Not for potentially hazardous food. The Food Standards Code requires it to be stored at 5°C or below unless the business can show that a specific food stays safe at a higher temperature. The FSANZ guide cites raw meat carcasses at 7°C maximum surface temperature under AS 4696-2007, but that is a meat processing standard, not a general allowance for a kitchen or retail cool room. A drinks-only cool room at 7°C is a quality question, not a food safety one.

What temperature should a commercial freezer be in Australia?

The Food Standards Code does not set a freezer temperature. It requires food intended to be stored frozen to remain frozen, which FSANZ describes as frozen hard. −18°C or colder is the figure manufacturers and the industry work to, so most commercial freezers are set between −18°C and −22°C. Follow the storage instructions on the product.

What temperature should a fridge be in Australia for food safety?

The food inside must be at 5°C or below. Most kitchens set reach-in fridges to 2–4°C so the food stays under 5°C when the door is opened during service. The set point is industry practice; the 5°C limit on the food is the legal requirement.

How often do I need to check cool room and fridge temperatures?

Category one food service businesses under Standard 3.2.2A must make a record of potentially hazardous food in storage, and FSANZ suggests doing it daily, keeping each record for 3 months. Most food safety programs check at least twice a day. Vaccine fridges are checked twice daily under Strive for 5, even when a data logger is fitted.

Does the thermostat display count as a temperature record?

Only as a guide to how the unit is running. FSANZ notes that fixed thermometers show the operating temperature of the unit, not the temperature of the food, and that food should be checked directly with a probe. A calibrated gauge, a logger graph or a probe in a product simulant can all support a storage record.